this site all sites
 english  hungarian   | Sitemap
Lossnay Klimagerät
aircon systems
CEILING CONCEALED DUCTED UNITS
USEFUL INFORMATION

 

LGH-Series

 

 

Lossnay Klimagerät

 

 

Advantages

Super-thin paper thickness in the heat exchanger, only 25 µm. 98% of the cooling/heating energy is transferred from exhaust to fresh air.
Humidifies/dehumidifies fresh air introduced into the room.
The supply and extract air ducts are separate to prevent the mixing of used and fresh air.
As a result of heat exchange with the exhaust air, the supply air is heated or cooled according to room conditions.
Minimum maintenance needs.

 

 

 

 

 

 

Easy-to-replace Lossnay element.
With its new control electronics, it can be connected directly to the air conditioners of the Mr. Slim Series with the A Control and the City Multi systems.
Additional heating directly controllable (relay to be supplied by the customer).
Special Lossnay remote control optional, see accessories.

 

 

Type   LGH-15RX4 LGH-25RX4 LGH-35RX4 LGH-50RX4 LGH-65RX4
Air flow rate (m³/h) Low High Extra-high 110
150
150
165
250
250
230
350
350
350
500
500
500
650
650
Static pressure (Pa)* Low High Extra-high 35
60
95
25
50
80
25
70
150
30
60
150
30
50
110
Noise level dB(A)** Low High Extra-high 22.0
24.0
26.0
22.0
25.0
26.5
23.0
28.0
31.0
23.5
29.5
33.0
27.0
32.5
34.5
Efficiency (%) Low High Extra-high 81.0
77.0
77.0
83.5
78.0
78.0
84.0
79.0
79.0
82.0
77.0
77.0
79.0
76.0
76.0
Weight (kg)   17 21 30 33 46
Abmessungen (mm) Width Depth Height 610
780
275
735
780
275
874
888
317
1016
888
317
954
908
388
Electrical supply
(V, phase, Hz)
  220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50
Power consumption (W) Low High Extra-high 45
63
92
52
85
103
97
154
169
123
193
204
185
270
295
Max. operating current (A)   0.45 0.49 0.79 0.95 1.4
Duct size Ø (mm)   100 150 150 200 200

 

Bezeichnung   LGH-80RX4 LGH-100RX4 LGH-150RX4 LGH-200RX4
Air flow rate (m³/h) Low High Extra-high 670
800
800
870
1000
1000
1250
1500
1500
1650
2000
2000
Static pressure (Pa)* Low High Extra-high 70
100
140
80
100
160
70
100
140
65
90
150
Noise level dB(A)** Low High Extra-high 30.0
32.0
33.5
31.5
34.0
36.0
32.5
35.5
36.5
35.0
37.0
39.0
Efficiency (%) Low High Extra-high 80.5
78.0
78.0
81.0
79.0
79.0
81.5
79.0
79.0
81.5
79.0
79.0
Weight (kg)   61 69 124 140
Abmessungen (mm) Width Depth Height 1004
1164
398
1231
1164
398
1004
1164
800
1231
1164
800
Electrical supply
(V, phase, Hz)
  220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50
Power consumption (W) Low High Extra-high 290
340
365
365
440
455
575
670
720
755
910
945
Max. operating current (A)   1.7 2.1 3.3 4.3
Duct size Ø (mm)   250 250 250/270 250/270
           

* For the given air flow rate
** Noise level measured centrally at a distance of 1.5 m beneath the unit
The details given as Low, High and Extra-high refer to the low, high and extra-high fan levels.
The fan level can be alternatively switched from High to Extra-high by means of DIP switches in order to increase the static pressure.


Seite empfehlen Seite drucken

 

 

City Multi VRF Series

City Multi VRF The City Multi Series is ideal for large and challenging buildings ... more

 

 

 

Reference catalogue
    (PDF 7.33 MB)

Reference catalogue Mitsubishi Electric creates an air of well-being wherever people live and work ... more

 

 

 


The paper cross-flow heat exchanger

paper cross-flow heat exchanger

All information to be found here