Heat pump systems
with split Zubadan inverter | R410A
|
|

Set EH-S20-HRP80-140
|
| |
|
Benefits
- 100% heating capacity down to an outdoor temperature of -15°C thanks to patented refrigerant circuit with HIC supercooler and compressor with flash injection. An immersion heater is no longer necessary.
- Extended temperature range down to -25°C
- Flow temperatures up to 60°C, thus also ideal for building modernization
- Full-scale heating controller integrated in the water tank, with an automatic calorimeter, controllable mixed heating circuit, screed heating programme, override button, anti-legionella circuit
|
|
- Ready-integrated energy-saving, electronically controlled circulation pump and an electric back-up heater for emergency activation
- Accelerated defrosting
- Compact outdoor unit for inconspicuous installation
- Outdoor unit with integrated plate heat exchanger
- Flexibly adjustable super-quiet mode
- Signal output for condensation drain heating (optional)
|
| Designation of set |
EH-S20-HRP80V |
EH-S20-HRP112V |
EH-S20-HRP112Y |
EH-S20-HRP140Y |
| Water tank volume (l) |
200 |
200 |
200 |
200 |
| Dimensions in mm (W/T/H) |
600 / 734 / 1699 |
600 / 734 / 1699 |
600 / 734 / 1699 |
600 / 734 / 1699 |
| Weight (kg) |
210 |
210 |
210 |
210 |
| Electrical supply (V, phase, Hz) |
220-240, 1, 50 |
220-240, 1, 50 |
220-240, 1, 50 |
220-240, 1, 50 |
| Water pipe size Ø (mm) |
22 x 1 |
22 x 1 |
22 x 1 |
22 x 1 |
| Outdoor unit type |
PUHZ-HRP71VHA |
PUHZ-HRP100VHA |
PUHZ-HRP100YHA |
PUHZ-HRP125YHA |
Heating capacity A2/W35 (kW)
Heating power consumption A2/W35 (kW)
Heating COP A2/W35 |
8.10
2.50
3.20 |
11.20
3.71
3.02 |
11.20
3.71
3.02 |
14.0
5.19
2.70 |
Heating capacity A7/W35 (kW)
Heating power consumption A7/W35 (kW)
Heating COP A7/W35 |
8.00
1.82
4.40 |
11.20
2.63
4.26 |
11.20
2.63
4.26 |
14.00
3.32
4.22 |
| Heating capacity A-15/W35 (kW) |
8.10 |
11.20 |
11.20 |
14.0 |
| Noise level (dB(A)) |
52 |
52 |
52 |
52 |
| Dimensions in mm (W/T/H) |
950 / 330 / 1350 |
950 / 330 / 1350 |
950 / 330 / 1350 |
950 / 330 / 1350 |
| Weight (kg) |
120 |
135 |
135 |
135 |
| Total pipe length (m) |
75 |
75 |
75 |
75 |
| Max. height difference (m) |
30 |
30 |
30 |
30 |
| Refrigerant charge (kg)* |
5.5 |
5.5 |
5.5 |
5.5 |
Refrigerant pipe size Ø (mm)
fl. / s. |
10 / 16 |
10 / 16 |
10 / 16 |
10 / 16 |
| Electrical supply (V, phase, Hz) |
220-240, 1, 50 |
220-240, 1, 50 |
380-415, 3, 50 |
380-415, 3, 50 |
| Operating current (A) |
8.2 |
11.7 |
4.0 |
5.3 |
| Circuit breaker (A) |
32 |
32 |
16 |
16 |
* Supplied refrigerant charge sufficient for 30 m pipe length (one way).