diese Seite alle Seiten
 english  hungarian   | Sitemap
Entspannung drei Kinder Klimageräte Ecodan
aircon systems
ECODAN SPLIT SYSTEMS
 

 

Heat pump systems with
split power inverter | R410A


 

 

EH-S20-RP105/115Y EH-S20-RP68/75V Klimagerät Wärmepumpe
Set EH-S20-RP68/75V | Set EH-S20-RP105/115                               

 

 


Benefits

  • Full-scale heating controller integrated in the water tank, with an automatic calorimeter, controllable mixed heating circuit, screed heating programme, override button, anti-legionella circuit

  • Ready-integrated energy-saving, electronically controlled circulation pump and an electric back-up heater to cover short-term consumption peaks are

  • Guaranteed operating range down to an outdoor temperature of -20°C
 


  • Flow temperatures up to 55°C

  • Ideal for building modernization thanks to high flow temperatures

  • Compact outdoor unit for inconspicuous installation

  • Pipe lengths up to 75 m for flexible outdoor installation

  • No water pipes have to be laid outdoors, so no risk of freezing
Designation of set EH-S20-RP68V EH-S20-RP75V EH-S20-RP105Y EH-S20-RP115Y
Water tank volume (l) 200 200 200 200
Dimensions in mm (W/T/H) 600 / 734 / 1699 600 / 734 / 1699 600 / 734 / 1699 600 / 734 / 1699
Weight (kg) 210 210 210 210
Electrical supply (V, phase, Hz) 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50
Water pipe size Ø (mm) 22 x 1 22 x 1 22 x 1 22 x 1

 

Outdoor unit type PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100YKA PUHZ-RP125YKA
Heating capacity A2/W35 (kW)
Heating power consumption A2/W35 (kW)
Heating COP A2/W35
6.80
2.31
2.94
7.50
2.57
2.92
10.50
3.62
2.90
11.50
4.26
2.70
Heating capacity A7/W35 (kW)
Heating power consumption A7/W35 (kW)
Heating COP A7/W35
7.00
1.63
4.29
8.00
1.90
4.21
11.20
2.66
4.21
14.00
3.37
4.15
Heating capacity A-15/W35 (kW) 4.20 4.20 5.80 6.90
Noise level (dB(A)) 48 48 51 52
Dimensions in mm (W/T/H) 950 / 330 / 943 950 / 330 / 943 1050 / 330 / 1338 1050 / 330 / 1338
Weight (kg) 67 75 124 126
Total pipe length (m) 50 50 75 75
Max. height difference (m) 30 30 30 30
Refrigerant charge (kg)* 3.5 3.5 5.0 5.0
Refrigerant pipe size Ø (mm)
fl. / s.
10 / 16 10 / 16 10 / 16 10 / 16
Electrical supply (V, phase, Hz) 220-240, 1, 50 220-240, 1, 50 380-415, 3, 50 380-415, 3, 50
Operating current (A) 7.2 8.4 4.1 5.2
Circuit breaker (A) 25 25 16 16

* Supplied refrigerant charge sufficient for 30 m pipe length (one way).
Noise level measured at a distance of 1 metre from the unit and at a height of 1 m.

 

Seite empfehlen Seite drucken