Heat pump systems with
split power inverter | R410A
|
|

Set EH-S20-RP68/75V | Set EH-S20-RP105/115
|
| |
|
Benefits
- Full-scale heating controller integrated in the water tank, with an automatic calorimeter, controllable mixed heating circuit, screed heating programme, override button, anti-legionella circuit
- Ready-integrated energy-saving, electronically controlled circulation pump and an electric back-up heater to cover short-term consumption peaks are
- Guaranteed operating range down to an outdoor temperature of -20°C
|
|
- Flow temperatures up to 55°C
- Ideal for building modernization thanks to high flow temperatures
- Compact outdoor unit for inconspicuous installation
- Pipe lengths up to 75 m for flexible outdoor installation
- No water pipes have to be laid outdoors, so no risk of freezing
|
| Designation of set |
EH-S20-RP68V |
EH-S20-RP75V |
EH-S20-RP105Y |
EH-S20-RP115Y |
| Water tank volume (l) |
200 |
200 |
200 |
200 |
| Dimensions in mm (W/T/H) |
600 / 734 / 1699 |
600 / 734 / 1699 |
600 / 734 / 1699 |
600 / 734 / 1699 |
| Weight (kg) |
210 |
210 |
210 |
210 |
| Electrical supply (V, phase, Hz) |
220-240, 1, 50 |
220-240, 1, 50 |
220-240, 1, 50 |
220-240, 1, 50 |
| Water pipe size Ø (mm) |
22 x 1 |
22 x 1 |
22 x 1 |
22 x 1 |
| Outdoor unit type |
PUHZ-RP60VHA |
PUHZ-RP71VHA |
PUHZ-RP100YKA |
PUHZ-RP125YKA |
Heating capacity A2/W35 (kW)
Heating power consumption A2/W35 (kW)
Heating COP A2/W35
|
6.80
2.31
2.94 |
7.50
2.57
2.92 |
10.50
3.62
2.90 |
11.50
4.26
2.70 |
Heating capacity A7/W35 (kW)
Heating power consumption A7/W35 (kW)
Heating COP A7/W35
|
7.00
1.63
4.29 |
8.00
1.90
4.21 |
11.20
2.66
4.21 |
14.00
3.37
4.15 |
| Heating capacity A-15/W35 (kW) |
4.20 |
4.20 |
5.80 |
6.90 |
| Noise level (dB(A)) |
48 |
48 |
51 |
52 |
| Dimensions in mm (W/T/H) |
950 / 330 / 943 |
950 / 330 / 943 |
1050 / 330 / 1338 |
1050 / 330 / 1338 |
| Weight (kg) |
67 |
75 |
124 |
126 |
| Total pipe length (m) |
50 |
50 |
75 |
75 |
| Max. height difference (m) |
30 |
30 |
30 |
30 |
| Refrigerant charge (kg)* |
3.5 |
3.5 |
5.0 |
5.0 |
Refrigerant pipe size Ø (mm)
fl. / s. |
10 / 16 |
10 / 16 |
10 / 16 |
10 / 16 |
| Electrical supply (V, phase, Hz) |
220-240, 1, 50 |
220-240, 1, 50 |
380-415, 3, 50 |
380-415, 3, 50 |
| Operating current (A) |
7.2 |
8.4 |
4.1 |
5.2 |
| Circuit breaker (A) |
25 |
25 |
16 |
16 |
* Supplied refrigerant charge sufficient for 30 m pipe length (one way).